VMC24-40, 24 kV
The VMC24-40 is a metal-clad vacuum switchgear using the 40kA VECTOR24-S40 VCB. Essentially of the same design as the
VMC12-40 and VMC18-40, but with bigger dimensions for higher insulation levels, the VMC24-40 is designed for use as primary distribution switchgear.| Parameters |
Unit |
VMC24-40 |
|
Rated Voltage |
kV |
24 |
|
Maximum service voltage |
kV |
24 |
|
Withstand Voltage to earth/between phases |
kV |
50 |
|
Withstand Voltage across isolating gap |
kV |
65 |
|
Impulse withstand voltage to earth/between phases |
kV |
125 |
|
Impulse withstand voltage cross isolating gap |
kV |
145 |
|
Rated Current |
A |
1600/2000/2500 |
|
Breaking capacity |
kA |
40 |
|
Breaking capacity for no-load transformers and cables |
A |
25 |
|
Short-time withstand current (R.M.S) |
kA/sec |
40/4 |
|
Peak withstand current |
kA |
80 |
|
Making Capacity |
kA |
80 |
|
Mechanical Endurance |
cycles |
20000 |
|
Electrical Endurance |
cycles |
10000 |
| Standard operating duty |
O-180s-CO-180s-CO |
|
| Rapid reclosing duty |
O-0.3sec-CO-0.3sec-CO |
|
|
Minimum panel width |
mm |
1000 |
|
Minimum panel height |
mm |
2200 |
|
Minimum panel depth |
mm |
1700 |
| The following represent only some of the schemes available for the VMC-S40/50 series Metal-clad Switchgear. For the full range of options please refer to the VMC/Vector product catalogue. |
|
![]() |
|
| Scheme nos: VMC-1 | ( Withdrawable VCB, 3xCT) | |
|
Rated Voltage |
Minimum Dimensions (WXDXH) mm |
|
|
12 kV |
750X1600X2100 |
|
|
17.5 kV |
850X1700X2200 |
|
|
24 kV |
950X1800X2300 |
|
|
Main switch apparatus: Standard features: |
Vector-S12, Vector-S18, Vector-S24 from 40kA to 50kA Optional features: |
|
|
|
|
|
![]() |
|
| Scheme nos: VMC-2 | ( Withdrawable VCB, 3xCT, Earth Switch) | |
|
Rated Voltage |
Minimum Dimensions (WXDXH) mm |
|
|
12 kV |
750X1600X2100 |
|
|
17.5 kV |
850X1700X2200 |
|
|
24 kV |
950X1800X2300 |
|
|
Main switch apparatus: Standard features: |
Vector-S12, Vector-S18, Vector-S24 from 40kA to 50kA Optional features: |
|
|
|
|
|
![]() |
|
| Scheme nos: VMC-3 | ( Withdrawable VCB, 3xCT, Voltage Indicators ) | |
|
Rated Voltage |
Minimum Dimensions (WXDXH) mm |
|
|
12 kV |
750X1600X2100 |
|
|
17.5 kV |
850X1700X2200 |
|
|
24 kV |
950X1800X2300 |
|
|
Main switch apparatus: Standard features: |
Vector-S12, Vector-S18, Vector-S24 from 40kA to 50kA Optional features: |
|
|
|
|
|
![]() |
|
| Scheme nos: VMC-4 | ( Withdrawable VCB, 3xCT,Surge Arrestors ) | |
|
Rated Voltage |
Minimum Dimensions (WXDXH) mm |
|
|
12 kV |
750X1600X2100 |
|
|
17.5 kV |
850X1700X2200 |
|
|
24 kV |
950X1800X2300 |
|
|
Main switch apparatus: Standard features: |
Vector-S12, Vector-S18, Vector-S24 from 40kA to 50kA Optional features: |
|
|
|
|
|
![]() |
|
| Scheme nos: VMC-5 | ( Withdrawable VCB, 3xCT, Surge Arrestors,Voltage Indicators ) | |
|
Rated Voltage |
Minimum Dimensions (WXDXH) mm |
|
|
12 kV |
750X1600X2100 |
|
|
17.5 kV |
850X1700X2200 |
|
|
24 kV |
950X1800X2300 |
|
|
Main switch apparatus: Standard features: |
Vector-S12, Vector-S18, Vector-S24 from 40kA to 50kA Optional features: |
|
|
|
|
|
![]() |
|
| Scheme nos: VMC-6 | ( Withdrawable VCB, 3xCT, Earth Switch,Voltage Indicators ) | |
|
Rated Voltage |
Minimum Dimensions (WXDXH) mm |
|
|
12 kV |
750X1600X2100 |
|
|
17.5 kV |
850X1700X2200 |
|
|
24 kV |
950X1800X2300 |
|
|
Main switch apparatus: Standard features: |
Vector-S12, Vector-S18, Vector-S24 from 40kA to 50kA Optional features: |
|
|
|
|
|
![]() |
|
| Scheme nos: VMC-7 | ( Withdrawable VCB, 3xCT, Earth Switch, Surge Arrestors ) | |
|
Rated Voltage |
Minimum Dimensions (WXDXH) mm |
|
|
12 kV |
750X1600X2100 |
|
|
17.5 kV |
850X1700X2200 |
|
|
24 kV |
950X1800X2300 |
|
|
Main switch apparatus: Standard features: |
Vector-S12, Vector-S18, Vector-S24 from 40kA to 50kA Optional features: |
|
|
|
|
|
![]() |
|
| Scheme nos: VMC-8 | ( Withdrawable VCB, 3xCT, Earth Switch, Surge Arrestors, Voltage Indicators ) | |
|
Rated Voltage |
Minimum Dimensions (WXDXH) mm |
|
|
12 kV |
750X1600X2100 |
|
|
17.5 kV |
850X1700X2200 |
|
|
24 kV |
950X1800X2300 |
|
|
Main switch apparatus: Standard features: |
Vector-S12, Vector-S18, Vector-S24 from 40kA to 50kA Optional features: |
|
|
|
|
- Medium Voltage Products
- Description
- Outdoor Switchgear
- Indoor Switchgear
- Circuit Breakers & Switches
- High Voltage Products
- Power Automation Products
- Cast-Resin Transformers
- Services