Vector12-S (Encapsulated Poles,Spring Mechanism driven)
The Vector12-S withdrawable VCB features the following:
- Phase-centre distances at 165mm for 1250A ratings, at 230mm for breakers with 2000A ratings and 280mm for breakers with ratings of 3150A and above.
- Designed to be mounted within LKE's Vector-VMC12 metal-clad switchgear.
- Encapsulated poles with vacuum interrupters embedded within the resin material of the pole housing to increase creepage distances and surface insulation between terminals.
- Nominal current ratings of up to 3150A with natural cooling and higher ratings are available with fan assisted cooling.
- Maximum breaking capacity of up to 40kA.
- Driven by conventional spring mechanism capable of more than 50,000 operations.

(Top) The Vector12-S32-1250/ with rated current level of 1250A. (Bottom) The Vector12-S32-3150/ with rated current level of 3150A
The VECTOR12-S has the following parameters:
| Electrical Characteristics | Unit | VECTOR12-S25 | VECTOR12-S31.5 | VECTOR12-S40 |
|---|---|---|---|---|
| Rated Voltage | kV | 12 | 12 | 12 |
| Rated current | A | 630~3150 | 630~3150 | 630~3150 |
| Short-time(1min) power frequecy withstand voltage Between phases, from phase to earth, and vacuum interrupter | kV | 42 | 42 | 42 |
| Lightning Impulse test voltage | kV | 95 | 95 | 95 |
| Rated maximum short-circuit breaking capacity | kA | 25 | 31.5 | 40 |
| Rated short-time current (kA X sec) | kA/s | 25/4 | 31.5/4 | 40/4 |
| Rated peak withstand current | kA | 50 | 65 | 80 |
| Rated single capacitor bank breaking current | A | 630 | 630 | 630 |
| Rated back-to-back capacitor bank breaking current | A | 400 | 400 | 400 |