LCA-G 12~24 kV(SF6 Switch)

The LCA-G is an extensible 12-24 kV AIS for the GLBS SF6 LBS. It is used on secondary distribution systems where switching demands are stringent and space limitations are severe. The load break switch is capable of breaking overload currents of up to 2600A at 12kV, while the fuse-combination provides protection from short-circuit currents of up to 31.5 kA at 12kV. Compatible with all other panels of the LCA series, it is also compatible with the IV2000(VCB).
lca-g2
General features include :
  • Nominal current until 630A.
  • Max breaking capacity 31.5kA,
  • S.C withstand capability at (rms) 20 kA/2sec
Panel Dimensions (WXDXH) :
  • 12kV: 375X1000X1850 mm
  • 17.5kV: 450X1000X1950 mm
  • 24kV: 550X1100X2050 mm
Parameters

Unit

12kV LCA-G

17.5 kV LCA-G

24kV LCA-G

Rated Voltage

kV

12

17.5

24

Maximum service voltage

kV

12

17.5

24

Withstand Voltage to earth/between phases

kV

28

38

50

Withstand Voltage across isolating gap

kV

32

45

60

Impulse withstand voltage to earth/between phases

kV

75

95

125

Impulse withstand voltage cross isolating gap

kV

85

110

145

Rated Current

A

630

630

630

Breaking capacity for no-load transformers

A

16

16

16

Breaking capacity for no-load lines and cables

A

25

25

25

Short-time current (for AL or BL type without fuses)

kA

20/2sec

20/2sec

20/2sec

Making Capacity

kA

50

50

50

Prospective breaking capacity (with fuses)

kA

31.5

31.5

31.5

Breaking capacity of main contacts (Transfer Current)

A

1500

1250

1000

Transfomer protection ratings

kVA

1250

800

630

Mechanical Endurance

cycles

2000

2000

2000

Electrical Endurance

cycles

300

300

300

Minimum panel width

mm

375

450

550

Minimum panel height

mm

1700

1850

1950

Minimum panel depth

mm

1000

1000

1100

The following represent only some of the schemes available for the LCA-G. For the full range of options please refer to the LCA-G product catalogue.

AL Mechanism BL Mechanism

Scheme nos: LCA--G1 ( Line-switch module )

Rated Voltage

Minimum Dimensions (WXDXH) mm

12 kV

375X1050X1550

17.5 kV

450X1050X1500

24 kV

550X1100X1500

Main switch apparatus: Standard features:

GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip -only with the GLBS-BL version
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G2 ( Line-switch module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1500

    17.5 kV

    450X1000X1600

    24 kV

    550X1100X1600

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Surge arrestors
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip -only with the GLBS-BL version
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G3 ( Line-switch module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1500

    17.5 kV

    450X1000X1600

    24 kV

    550X1100X1600

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage indicators
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip -only with the GLBS-BL version
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G4 ( Line-switch module with CTs)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1850

    24 kV

    550X1100X1950

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Current transformers
  • Ammeters
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip -only with the GLBS-BL version
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G5 ( Line-switch module)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1850

    24 kV

    550X1100X1950

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch
  • Voltage indicators
  • Surge Arrestors
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip -only with the GLBS-BL version
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G6 ( Line-switch module with CT)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1950

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • 1~3 X Current transformers
  • 1~3XAmmeters
  • Surge Arrestors
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip -only with the GLBS-BL version
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G7 ( Line-switch module with CT )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1950

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage indicators
  • 1~3 X Current transformers
  • 1~3XAmmeters
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip -only with the GLBS-BL version
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G8 ( Line-switch module with CT )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1950

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage indicators
  • 1~3 X Current transformers
  • 1~3XAmmeters
  • Surge Arrestors
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip -only with the GLBS-BL version
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G9 ( Inverted Line Switch)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1850

    24 kV

    550X1100X1950

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip with GLBS-BL only
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G10 ( Inverted Line Switch)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1850

    24 kV

    550X1100X1950

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Surge Arrestors
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip only with GLBS-BL
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G11 (Inverted Line Switch)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1850

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage indicators
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip only with GLBS-BL
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G12 ( Inverted Line Switch)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1850

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • 1~3 x Current Transformers
  • 1~3 x Ammeters
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip only with GLBS-BL
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G13 (Inverted Line Switch)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450x1000X1950

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage indicators
  • Surge Arrestors
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip available only with GLBS-BL
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G14 ( Inverted Line Switch )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1850

    17.5 kV

    450X1000X1950

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Surge Arrestors
  • 1~3xCurrent Transformers
  • 1~3xAmmeters
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G15 ( Inverted Line Switch )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1850

    17.5 kV

    450X1000X1950

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage Indicators
  • 1~3xCurrent Transformers
  • 1~3xAmmeters
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip only with GLBS-BL
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G16 ( Fuse-switch transformer protection module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1850

    17.5 kV

    450X1000X1950

    24 kV

    550X1100X2050

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage Indicators
  • Surge Arrestors
  • 1~3xCurrent Transformers
  • 1~3xAmmeters
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip only with GLBS-BL
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G17 ( Line Switch and T-type Cable Bushings )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1850

    24 kV

    550X11100X1950

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage indicators
  • T-type cable bushings
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip with GLBS-BL only
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • AL Mechanism BL Mechanism
    Scheme nos: LCA--G18 ( Line Switch and T-Type Cable Bushings)

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    375X1000X1750

    17.5 kV

    450X1000X1850

    24 kV

    550X1100X1950

    Main switch apparatus: Standard features:

    GLBS-AL or GLBS-BL Optional features:

  • Main switch & earth switch
  • Voltage indicators
  • T-type cable bushings
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip available only with GLBS-BL
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • BL Mechanism
    Scheme nos: LCA--G19 ( Fuse-switch transformer protection module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    450X1000X1750

    17.5 kV

    550X1000X1850

    24 kV

    600X1100X2050

    Main switch apparatus: Standard features:

    GLBS-BF Optional features:

  • Main switch & earth switch
  • Voltage indicators
  • Fuse-clamps & HRC Fuses
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • BF Mechanism
    Scheme nos: LCA--G20 ( Fuse-switch transformer protection module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    450X1000X1750

    17.5 kV

    550X1000X1850

    24 kV

    600X1100X2050

    Main switch apparatus: Standard features:

    GLBS-BF Optional features:

  • Main switch & earth switch
  • Fuse-clamps & HRC fuses
  • External earth-switch
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • BF Mechanism
    Scheme nos: LCA--G21 ( Fuse-switch transformer protection module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    450X1000X1750

    17.5 kV

    550X1000X1850

    24 kV

    600X1100X2050

    Main switch apparatus: Standard features:

    GLBS-BF Optional features:

  • Main switch & earth switch
  • Fuse-clamps & HRC fuses
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • BF Mechanism
    Scheme nos: LCA--G22 ( Fuse-switch transformer protection module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    450X1000X1750

    17.5 kV

    550X1000X1850

    24 kV

    600X1100X2050

    Main switch apparatus: Standard features:

    GLBS-BF Optional features:

  • Main switch & earth switch
  • Voltage Indicators
  • Fuse-clamps & HRC fuses
  • External earth-switch
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • BF Mechanism
    Scheme nos: LCA--G23 ( Fuse-switch transformer protection module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    450X1000X1750

    17.5 kV

    550X1000X1850

    24 kV

    600X1100X2150

    Main switch apparatus: Standard features:

    GLBS-BF Optional features:

  • Main switch & earth switch
  • Voltage Indicators
  • Surge Arrestors
  • Fuse-clamps & HRC fuses
  • External earth-switch
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive
  • BF Mechanism
    Scheme nos: LCA--G24 ( Fuse-switch transformer protection module )

    Rated Voltage

    Minimum Dimensions (WXDXH) mm

    12 kV

    450X1000X1750

    17.5 kV

    550X1000X1850

    24 kV

    700X1100X2150

    Main switch apparatus: Standard features:

    GLBS-BF Optional features:

  • Main switch & earth switch
  • Voltage Indicators
  • Surge Arrestors
  • 1~3XCurrent Transformers
  • 1~3XAmmeters
  • External earth-switch
  • Safety inter-locks
  • cable mounting rack
  • Observation window
  • operating handle
  • Door locks
  • Shunt trip
  • auxilliary contacts
  • interlock with adjacent switch
  • key interlocks
  • internal illumination
  • heater
  • motor and gear drive